Addr.
Parameter
C
Setting Options
Default Setting
_:751:8
Definite-T 1:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:751:3
Definite-T 1:Threshold
1 A @ 100 Irated 0.010 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.010 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.05 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.002 A to 8.000 A
6.000 A
_:751:4
Definite-T 1:Dropout
ratio
0.90 to 0.99
0.95
_:751:101
Definite-T 1:Dropout
delay
0.00 s to 60.00 s
0.00 s
_:751:6
Definite-T 1:Operate
delay
0.00 s to 60.00 s
0.30 s
Dyn.s: AR off/n.rdy
_:751:28
Definite-T 1:Effect. by AR
off/n.ready
•
no
•
yes
no
_:751:35
Definite-T 1:Stage
blocked
•
no
•
yes
no
Dyn.set: AR cycle 1
_:751:29
Definite-T 1:Effected by
AR cycle 1
•
no
•
yes
no
_:751:36
Definite-T 1:Stage
blocked
•
no
•
yes
no
_:751:14
Definite-T 1:Threshold
1 A @ 100 Irated 0.010 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.010 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.05 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.002 A to 8.000 A
6.000 A
_:751:20
Definite-T 1:Operate
delay
0.00 s to 60.00 s
0.30 s
Dyn.set: AR cycle 2
_:751:30
Definite-T 1:Effected by
AR cycle 2
•
no
•
yes
no
_:751:37
Definite-T 1:Stage
blocked
•
no
•
yes
no
_:751:15
Definite-T 1:Threshold
1 A @ 100 Irated 0.010 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.05 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.010 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.05 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.002 A to 8.000 A
6.000 A
_:751:21
Definite-T 1:Operate
delay
0.00 s to 60.00 s
0.30 s
Dyn.set: AR cycle 3
_:751:31
Definite-T 1:Effected by
AR cycle 3
•
no
•
yes
no
Protection and Automation Functions
7.5 Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual
643
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...