CFC
Typical response times and maximum number of ticks of the CFC task levels:
Task Level
Time (in ms)
Ticks CP200
Ticks CP300
Fast Event-Trig-
gered
< 1
1500
3000
Event-Triggered
<10
13 059
15 006
Interlocking
<10
123 927 in total
144 022 in total
Measurement
250
The times describe the response time of a typical CFC chart at the respective task level. The maximum number
of ticks applies to a typical load for the device based on the application template 6MD85 Standard (Double
busbar feeder with switchgear interlocking protection).
The task level
Measurement
runs in cycles every 500 ms. All other task levels are event-triggered.
In order to estimate the tick consumption of a CFC chart, you can use the following formula:
T
chart
= 5 ∙ n
Inp
+ 5 ∙ n
Outp
+ T
TLev
+ ∑
i
T
int
+ ∑
j
T
Block
where:
n
Inp
Number of indications routed as input in the CFC chart
n
Outp
Number of indications routed as output in the CFC chart
T
TLev
101 Ticks in Fast Event-Triggered Level
104 Ticks in Event-Triggered Level
54 Ticks in Measurement Level
74 Ticks in Interlocking Level
T
int
Number of internal connections between 2 CFC blocks in one chart
T
Block
Used ticks per CFC block (see Technical Data)
Table 11-7
Ticks of the Individual CFC Blocks
Element
Ticks
ABS_D
2.3
ABS_R
1.5
ACOS_R
6.9
ADD_D4
3.4
ADD_R4
3.3
ADD_XMV
6.4
ALARM
1.8
AND_SPS
1.1
AND10
2.9
APC_DEF
1.2
APC_EXE
1.0
APC_INFO
3.9
ASIN_R
1.3
ATAN_R
1.2
BLINK
1.3
BOOL_CNT
2.0
BOOL_INT
1.5
BSC_DEF
1.3
BSC_EXE
1.1
11.48
Technical Data
11.48 CFC
1200
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...