[scomvimp-010313-01.tif, 2, en_US]
Figure 9-32
Setting with DIGSI, General Settings, Pulse-Metered Values
Application and Setting Notes for Pulse-Metered Values
The functionality Pulse-metered values is not preconfigured. If you want to use the functionality, you must
load it from the library into the respective function group.
The parameters can be set individually for every pulse counter. You will find the setting parameters in DIGSI in
the project tree under Parameter > Function group
For pulse-metered values, the following described settings and binary inputs are available.
Parameter:
Restore time
•
Default setting:
(_:101) Restore time
=
none
Parameter Value
Description
none
Deactivated
hh:00
Transfer on the full hour
hh:15
Transfer 15 minutes after the full hour Note:
hh:30
Transfer 30 minutes after the full hour Note:
hh:45
Transfer 45 minutes after the full hour Note:
Note: If the parameter is activated through a time setting, the parameter
Restore interval
is not in effect
and will be deactivated automatically.
Parameter:
Restore interval
•
Default setting:
(_:102) Restore interval
=
0 min
9.10.2
Measured Values, Energy Values, and Supervision of the Primary System
9.10 User-Defined Metered Values
1046
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...