Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:6601:1
General:Mode
•
off
•
on
•
test
on
_:6601:101
General:79 operating mode
•
with op., w/o act. time
•
with op., with act. time
•
w.pickup, w/o act. time
•
w.pickup, w. action time
with op., with
act. time
_:6601:102
General:CB ready check bef.
start
•
no
•
yes
no
_:6601:103
General:Reclai. time
aft.succ.cyc.
0.50 s to 300.00 s
3.00 s
_:6601:104
General:Block. time aft.
man.close
0.00 s to 300.00 s
1.00 s
_:6601:105
General:Start signal
supervis.time
0.01 s to 300.00 s
0.13 s
_:6601:106
General:CB ready superv.
time
0.01 s to 300.00 s
3.00 s
_:6601:107
General:3-pole operate by
79
•
no
•
yes
yes
_:6601:111
General:Max. dead-time
extension
0.00 s to 300.00 s; ∞
1.20 s
_:6601:114
General:Voltage supervi-
sion time
0.10 s to 30.00 s
0.10 s
_:6601:115
General:Volt. thres.f. live
line/bus
0.300 V to 340.000 V
48.000 V
ADT
_:6631:101
ADT:1-pole trip allowed
•
no
•
yes
no
_:6631:104
ADT:Action time
0.00 s to 300.00 s; ∞
0.20 s
_:6631:105
ADT:Maximum dead time
0.50 s to 3000.00 s
5.00 s
_:6631:102
ADT:CB ready check
bef.close
•
no
•
yes
no
_:6631:103
ADT:Synchroch. aft. 3-pole
d.t.
•
none
•
internal
•
external
none
_:6631:106
ADT:Intern. synchrocheck
with
Setting options depend on
configuration
Information List
No.
Information
Data Class
(Type)
Type
General
_:6601:51
General:Mode (controllable)
ENC
C
_:6601:87
General:>Function off
SPS
I
_:6601:524
General:>Function on
SPS
I
_:6601:347
General:Function on
SPC
C
_:6601:82
General:>Block function
SPS
I
_:6601:501
General:>Release by ext.sync.
SPS
I
7.2.5.2
7.2.5.3
Protection and Automation Functions
7.2 Automatic Reclosing Function
SIPROTEC 5, High-Voltage Bay Controller, Manual
581
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...