Overvoltage Protection with 3-Phase Voltage
Setting Values for Stage Type Definite-Time Overvoltage Protection
Measured value
Phase-to-phase
Phase-to-ground
Method of measurement
Fundamental component
RMS value
Pickup mode
1 out of 3
3 out of 3
Pickup value
69
0.300 V to 340.000 V
Increments of 0.001 V
Time delay
0.00 s to 300.00 s
Increments of 0.01 s
Dropout ratio
0.90 to 0.99
Increments of 0.01
Setting Values for Stage Type Inverse-Time Overvoltage Protection
Measured value
Phase-to-phase
Phase-to-ground
Method of measurement
Fundamental component
RMS value
Pickup mode
1 out of 3
3 out of 3
Pickup value
0.300 V to 340.000 V
Increments of 0.001 V
Pickup factor
1.00 to 1.20
Increments of 0.01
Characteristic constant k
0.00 to 300.00
Increments of 0.01
Characteristic constant α
0.010 to 5.000
Increments of 0.001
Characteristic constant c
0.000 to 5.000
Increments of 0.001
Time multiplier
0.05 to 15.00
Increments of 0.01
Additional time delay
0.00 s to 60.00 s
Increments of 0.01 s
Reset time
0.00 s to 60.00 s
Increments of 0.01 s
Operate Curve for Stage Type Inverse-Time Overvoltage Protection
Where
T
op
Operate delay
T
inv
Inverse-time delay
T
add
Additional time delay (parameter
Additional time delay
)
Where
T
inv
Inverse-time delay
T
p
Time multiplier (parameter
Time dial
)
V
Measured voltage
11.17
69
If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.
Technical Data
11.17 Overvoltage Protection with 3-Phase Voltage
1150
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...