Signal Name
Description
Type
Op.ct.
The information counts the number of disconnector
switching cycles.
INS
Control
It is the task of the controls to execute command checks and establish communication between the command
source and the disconnector. Using the control settings, you specify how the commands are to be processed
(see also chapter
6.3.1 Command Checks and Switchgear Interlocking Protection
).
Through the function SBO (Select Before Operate, reservation
19
), the switching device is reserved prior to the
actual switching operation, thus it remains locked for additional commands. Feedback monitoring provides
information about the initiator of the command while the command is in process, that means, informing
whether or not the command was implemented successfully. These two options can be selected individually in
the selection of the control model, so that 4 combinations in total are available (see the following table).
The control makes the following settings available (see next table).
Parameters
Default Setting Possible Parameter Values
(_:4201:101) Control model
SBO w. enh.
security
20
direct w. normal secur.
SBO w. normal secur.
direct w. enh. security
SBO w. enh. security
(_:4201:102) SBO time-out
30.00 s
-
(_:4201:103) Feedback monitoring time
10.00 s
-
(_:4201:104) Check switching authority
yes
no
yes
advanced
(_:4201:105) Check if pos. is reached
yes
no
yes
(_:4201:106) Check double activat. blk. yes
no
yes
Trigger Variants of the Disconnector
The activation types are identical to those for the circuit breaker. The meaning of abbreviations can be found
in
6.2.2.3 Connection Variants of the Circuit Breaker
6.2.2.3 Connection Variants of the Circuit Breaker
Whether the disconnector is triggered for 1-, 1.5-, or 2-phases depends on the design of the auxiliary and
control voltage system.
1-Pole Triggering
[dw1ptren-030211-01.tif, 1, en_US]
Figure 6-20
1-Pole Triggering
6.2.3.3
19
In the IEC 61850 standard, Reservation is described as Select before Operate (SBO).
20
This default setting is the standard control model for a switching command in an IEC 61850-compliant system.
Control Functions
6.2 Switching Devices
SIPROTEC 5, High-Voltage Bay Controller, Manual
331
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...