Parameter:
Number of tap positions
•
Default setting
Number of tap positions
=
15
With the
Number of tap positions
parameter, you set the number of transformer taps. The range of
values extends from 2 to 127. The output of the tap position is limited from -63 to +63. If the number of taps
is > 63, set the
Tap-display offset
parameter so that the output of the tap position is within the range of
-63 to +63.
Parameter:
Tap-coding type
•
Default setting
Tap-coding type
=
binary
In the
Tap-coding type
list box, select the interpretation type of the indication pending at the binary input.
You can select from the following options:
•
binary
•
1-of-n
•
BCD
•
table
•
BCD signed
•
gray
A selection of tap-coding types is described in greater detail using examples in the following text.
Routing of the Binary Inputs (Tap-Coding Type binary)
The following table shows the routing of 3 binary inputs (BI 1 to BI 3) with 4 transformer tap positions desig-
nated 3 to 6. BI4 is the moving contact. The encoding is in
binary
.
Table 6-25
Routing of the Binary Inputs (Tap-Coding Type binary)
Example
BI1
BI2
BI3
BI4
BI5
BI6
Tap changer
X
X
X
X
Meaning
Bit 1
Bit 2
Bit 3
Moving
contact
Tap = 1
1
0
0
With 3 binary inputs, a maximum of 2
3
-1 = 7 tap positions can be mapped in binary code. If all routed binary
inputs indicate 0, this is interpreted as a connection error and is reported by Position --- or -64 with quality
invalid. The representation of transformer taps should start with the metered value 3. You must configure the
information properties as follows for the example:
Tap-coding type:
binary
Number of tap positions:
7
Number of bits f. tap code:
4
Tap-display offset:
2
Moving contact (highest binary input):
Yes
The 3 binary inputs must be numbered sequentially, for example, BI 1, BI 2, BI 3, and BI 4 for the moving
contact.
Routing of the Binary Inputs (Tap-Coding Type BCD)
The following table shows the routing of 6 binary inputs (BI 1 to BI 6) with 39 transformer tap positions desig-
nated 1 to 39. The encoding is in
BCD
. BI 7 is the moving contact.
Control Functions
6.8 Transformer Tap Changers
444
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...