The settings in primary and secondary values result in the following setting values which include a safety
margin of 10 %:
[foocpgr4-030311-01.tif, 3, en_US]
In case of short-circuit currents exceeding 1246 A (primary) or 10.39 A (secondary) there is a short-circuit on
the line to be protected. The overcurrent protection can cut off this short circuit immediately.
Note: The amounts in the calculation example are accurate enough for overhead lines. If the source impe-
dance, line impedance and zero-sequence impedance have very different angles, you have use complex
numbers to calculate the
Threshold
.
Parameter:
Dropout delay
•
Recommended setting value
(_:751:101) Dropout delay
=
0
This parameter is not visible in the basic stage.
Siemens recommends using the default setting
0
since the dropout of a protection stage must be done as fast
as possible.
You can use the
Dropout delay
parameter ≠
0
to obtain a uniform dropout behavior if you use it together
with an electromechanical relay. This is required for time grading. The dropout time of the electromechanical
relay must be known for this purpose. Subtract the dropout time of your own device (see Technical Data) and
set the result.
Parameter:
Dropout ratio
•
Recommended setting value
(_:751:4) Dropout ratio
=
0.95
This parameter is not visible in the basic stage.
The recommended set value of
0.95
is appropriate for most applications.
To achieve high-precision measurements, the setting value of the parameter
Dropout ratio
can be
reduced, for example, to
0.98
. If you expect highly fluctuating measurands at the response threshold, you
can increase the setting value of the parameter
Dropout ratio
. This avoids chattering of the tripping stage.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:2311:101
General:Emergency
mode
•
no
•
caused by main prot.
•
caused by binary input
no
_:2311:9
General:Measured value
•
3I0 calculated
•
IN measured
IN measured
General
_:751:1
Definite-T 1:Mode
•
off
•
on
•
test
off
_:751:2
Definite-T 1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:751:26
Definite-T 1:Dynamic
settings
•
no
•
yes
no
_:751:27
Definite-T 1:Blk. w.
inrush curr. detect.
•
no
•
yes
no
7.5.4.3
Protection and Automation Functions
7.5 Overcurrent Protection, Ground
642
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...