selectively. The integrals are referred to the squared rated normal current of the circuit breaker as shown in
the following formula, with phase A as example.
[FoCBWI2T-301012-01.tif, 1, en_US]
Where:
I
rated
Rated normal current
i
A
(t)
Sampled measured current value of phase A
The calculated squared tripping current integrals are added to the existing statistic values.You can reset or
preset the statistic value according to the specific application.
Circuit-Breaker Maintenance Warning
If the statistic value of any phase lies above the threshold, a phase-selective warning signal is generated.
Application and Setting Notes
Parameter:
Threshold
•
Default setting
(_:101) Threshold
=
10 000.00 I/Ir*s
You use the
Threshold
parameter to specify the maximum permitted integral of squared sampled measured
values of the phase currents.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
I2t-method
_:1
I2t-method:Mode
•
off
•
on
•
test
off
_:101
I2t-method:Threshold
0.00 I/Ir*s to 21400000.00 I/Ir*s 10000.00 I/Ir*s
Information List
No.
Information
Data Class
(Type)
Type
I2t-method
_:54
I2t-method:Inactive
SPS
O
_:52
I2t-method:Behavior
ENS
O
_:53
I2t-method:Health
ENS
O
_:301
I2t-method:ΣI²t A
BCR
O
_:302
I2t-method:ΣI²t B
BCR
O
_:303
I2t-method:ΣI²t C
BCR
O
_:304
I2t-method:Warning
ACT
O
9.6.6.2
9.6.6.3
9.6.6.4
Measured Values, Energy Values, and Supervision of the Primary System
9.6 Circuit-Breaker Wear Monitoring
SIPROTEC 5, High-Voltage Bay Controller, Manual
1033
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...