Parameter Value
Description
IEC 60870-5-103
The time is synchronized via telegram with an appropriately configured
communication interface in accordance with the IEC 60870-5-103 protocol.
Time zone time source 1
or
Time zone time source 2
=
local
However, there are also T103 systems that send the UTC.
DNP3
The time is synchronized via telegram with the appropriately configured
communication interface in accordance with the DNP3 protocol.
Two characteristics are supported in the process:
•
Time synchronization via UTC
•
Time synchronization with local time
The daylight saving time status is not transmitted. The device assumes that
the DNP3 master follows the same rules for the start and end of the
daylight saving time as those that were set for the device.
Time zone time source 1
or
Time zone time source 2
=
UTC
is
the current implementation,
local
concerns older implementations.
IEEE 1588
Time is synchronized via an IEEE 1588 timing master. In this case, SIPROTEC 5
devices operate as slave-only clocks. IEEE 1588 v2 is supported with P2P and
Ethernet Transport.
The IEEE 1588 service must be enabled during configuration of Ethernet inter-
faces so that it is available as an option for the time synchronization.
Time zone time source 1
or
Time zone time source 2
=
UTC
.
Parameter: Fault indication after
•
Default setting
Fault indication after
=
600 s
With the
Fault indication after
parameter, you set the time delay after which the unsuccessful
attempts of time synchronization with external time sources configured are indicated.
Parameter: Time Zone and Daylight Saving Time
This parameter block contains all the settings for the local time zone and daylight saving time of your
SIPROTEC 5 device. In addition to the individual parameters, configure the basic settings by preselecting via
the radio buttons or check box.
[sctimezo-210415, 1, en_US]
Figure 3-72
Settings for Time Zone and Daylight Saving Time in DIGSI
System Functions
3.6 Date and Time Synchronization
134
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...