Addr.
Parameter
C
Setting Options
Default Setting
_:4861:15
Definite-T 1:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:4861:21
Definite-T 1:Operate
delay
0.00 s to 60.00 s
0.30 s
Dyn.set: AR cycle 3
_:4861:31
Definite-T 1:Effected by
AR cycle 3
•
no
•
yes
no
_:4861:38
Definite-T 1:Stage
blocked
•
no
•
yes
no
_:4861:16
Definite-T 1:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:4861:22
Definite-T 1:Operate
delay
0.00 s to 60.00 s
0.30 s
Dyn.s: AR cycle>3
_:4861:32
Definite-T 1:Effected by
AR cycle gr. 3
•
no
•
yes
no
_:4861:39
Definite-T 1:Stage
blocked
•
no
•
yes
no
_:4861:17
Definite-T 1:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:4861:23
Definite-T 1:Operate
delay
0.00 s to 60.00 s
0.30 s
Dyn.s: Cold load PU
_:4861:33
Definite-T 1:Effect. b.
cold-load pickup
•
no
•
yes
no
_:4861:40
Definite-T 1:Stage
blocked
•
no
•
yes
no
_:4861:18
Definite-T 1:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:4861:24
Definite-T 1:Operate
delay
0.00 s to 60.00 s
0.30 s
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual
717
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...