Application Templates and Functional Scope for Device 6MD86
Application templates are available in DIGSI 5 for the applications of device 6MD86.
The application templates contain:
•
Basic configurations
•
Required functions
•
Default settings
The following application templates are available for the device 6MD86 in the DIGSI 5 function library:
•
Not preconfigured
•
Double busbar
•
1.5 circuit breaker, type 1
•
1.5 circuit breaker, type 2
To load the application templates to the device, the following minimum hardware configuration requirements
must be met:
Application Templates
Hardware Configuration
Template 1
Double busbar
8 binary inputs (BI), 15 binary
outputs (BO), 4 I, 4 V
Template 2
1.5 circuit breaker, type 1
42 BI, 38 BO, 8 I, 8 V
Template 3
1.5 circuit breaker, type 2
42 BI, 32 BO, 8 I, 8 V
The following table shows the functional scope and the function-point requirements of the application
templates described below:
Table 4-2
Functional Scope of the Application Templates for Device 6MD86
ANSI
Function
Abbr.
Points
Template 1
Template 2
Template 3
25
Synchrocheck, synchronizing function
0
x
x
x
27
Undervoltage protection, 3-phase
V<
5
27
Undervoltage protection, 3-phase,
universal, Vx
Vx<
5
32/37
Power protection active/reactive power
P<>, Q<>
10
38
Temperature supervision
θ>
0
46
Negative-sequence protection, non-direc-
tional
I
2
>
10
49
Thermal overload protection
θ, I
2
t
0
50/51 TD
Overcurrent protection, phases
I>
0
x
2
x
50N/51N TD
Overcurrent protection, ground
IN>
10
67
Directional time-overcurrent protection,
phases
I>, ∠ (V,I)
35
67N
Directional time-overcurrent protection,
ground
35
51V
Overcurrent protection, voltage-dependent t = f(V,I)
10
50HS
Instantaneous high-current tripping
I>>>
0
50BF
Circuit-breaker failure protection
15
x
59
Overvoltage protection, 3-phase
V>
5
4.3
Applications
4.3 Application Templates and Functional Scope for Device 6MD86
178
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...