Settings
Addr.
Parameter
C
Setting Options
Default Setting
V-release #
_:1
V-release #:Mode
•
off
•
on
•
test
off
_:2
V-release #:Operate &
flt.rec. blocked
•
no
•
yes
no
_:10
V-release #:Blk. by
meas.-volt. failure
•
no
•
yes
yes
_:27
V-release #:Blk. w. inrush
curr. detect.
•
no
•
yes
no
_:8
V-release #:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:3
V-release #:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A
7.50 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.500 A
5 A @ 50 Irated
0.15 A to 175.00 A
7.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.500 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
7.500 A
_:101
V-release #:Type of char-
acter. curve
•
ANSI long-time inv.
•
ANSI short-time inv.
•
ANSI extremely inv.
•
ANSI very inverse
•
ANSI normal inverse
•
ANSI moderately inv.
•
ANSI definite inverse
•
IEC normal inverse
•
IEC very inverse
•
IEC extremely inv.
•
IEC long-time inverse
IEC normal
inverse
_:102
V-release #:Reset
•
instantaneous
•
disk emulation
disk emulation
_:103
V-release #:Time dial
0.05 to 15.00
1.00
_:104
V-release #:Under-
voltage threshold
0.300 V to 175.000 V
75.000 V
Information List
No.
Information
Data Class
(Type)
Type
V-release #
_:81
V-release #:>Block stage
SPS
I
_:500
V-release #:>Block delay & op.
SPS
I
_:54
V-release #:Inactive
SPS
O
_:52
V-release #:Behavior
ENS
O
_:53
V-release #:Health
ENS
O
_:60
V-release #:Inrush blocks operate
ACT
O
_:59
V-release #:Disk emulation running
SPS
O
_:55
V-release #:Pickup
ACD
O
_:56
V-release #:Operate delay expired
ACT
O
_:57
V-release #:Operate
ACT
O
7.12.4.3
7.12.4.4
Protection and Automation Functions
7.12 Voltage-Dependent Overcurrent Protection
782
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...