Properties
Function
To Be Found in
Suppress intermediate
position
(yes/no)
When activated, only the inter-
mediate position is suppressed by
the duration of the software
filtering time.
Position of the Control function
block
16
Treatment of spontaneous
position changes
(Gen. Soft-
ware Filt./Spont. Software Filt.)
If you select the
General soft-
ware filter
setting, the general
settings for software filtering of
spontaneous position changes and
for position changes caused by a
switching command apply. By
selecting
Spontaneous soft-
ware filter
, a separate filtering
is activated for spontaneous posi-
tion changes.
Position of the Control function
block
16
Spontaneous software
filtering time
Software filtering time for sponta-
neous position changes
Position of the Control function
block
16
Spontaneous retrigger
filter
(yes/no)
Switching on/off retriggering of the
filtering time by spontaneous posi-
tion change
Position of the Control function
block
16
Spontaneous indication
timestamp before filtering
(yes/no)
Consideration of the hardware
filtering time for position-detection
time stamp in case of a sponta-
neous change
Position of the Control function
block
16
Inhibit intermediate posi-
tion for a spontaneous
chng.
(yes/no)
When activated, only the sponta-
neous change to the intermediate
position is suppressed by the dura-
tion of the software filtering time.
Position of the Control function
block
16
Table 6-3
Setting Options of the Controllable
Position
in the Circuit-Breaker Function Block (Chatter
Blocking)
Properties
Function
To Be Found in
Chatter blocking
(yes/no)
Switching chatter blocking on/off
Position of the Circuit-breaker
function block
16
Table 6-4
Additional Settings in the Device Settings having Effects on the Circuit Breaker
Properties
Function
To Be Found in
Number of permissible
status changes
Chatter-blocking setting value:
Once for the entire device
Device settings (to be found under
Settings)
Chatter test time
Number of chatter tests
Chatter idle time
Chatter check time
The inputs and outputs as well as the setting options of the Circuit-breaker and Control function blocks are
described in the next section (see
6.2.2.3 Connection Variants of the Circuit Breaker
).
Interlocking
The
Interlocking
function block generates the releases for switchgear interlocking protection. The actual
interlocking conditions are deposited in CFC. For more information on this, see the overreaching chapter
6.3.1 Command Checks and Switchgear Interlocking Protection
.
Control Functions
6.2 Switching Devices
310
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...