Parameter Value
Description
on
Because of the application, it makes sense that the stage is only active (that
is, not blocked) when a certain current flow is present (see note).
off
Current flow monitoring does not make sense for the application.
i
i
NOTE
Because of the flexible setting options of the voltage measurand, the function itself does not determine the
current associated with the voltage. A suitable current-flow monitoring function must be created by the
user with the Continuous Function Chart (CFC), and connected to the binary input signal
>Current
flow-criterion
.
Operation as Supervision Function
If you want the tripping stage to have a reporting effect only, generation of the operate indication and fault
logging can be disabled via the
Operate & flt.rec. blocked
parameter.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:2311:101
General:Current-flow
criterion
•
off
•
on
on
Stage 1
_:571:1
Stage 1:Mode
•
off
•
on
•
test
off
_:571:2
Stage 1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:571:9
Stage 1:Measured value
•
VA measured
•
VB measured
•
VC measured
•
VAB measured
•
VBC measured
•
VCA measured
•
VAB calculated
•
VBC calculated
•
VCA calculated
•
V0 calculated
VA measured
_:571:8
Stage 1:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:571:3
Stage 1:Threshold
0.300 V to 340.000 V
80.000 V
_:571:4
Stage 1:Dropout ratio
1.01 to 1.20
1.05
_:571:6
Stage 1:Operate delay
0.00 s to 60.00 s
3.00 s
Stage 2
_:572:1
Stage 2:Mode
•
off
•
on
•
test
off
_:572:2
Stage 2:Operate &
flt.rec. blocked
•
no
•
yes
no
7.17.5
Protection and Automation Functions
7.17 Undervoltage Protection with Any Voltage
822
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...