ments which can be used to determine the direction are available in the voltage memory, the basic stage
generally picks up without direction determination, that is non-directionally. For the advanced stage, the
response can be defined via the
Non-directional pickup
parameter. With the
at volt.< &
mem.empty
setting, the function picks up in such a situation without direction determination. With the
no
setting, the function does not pick up.
Directional Comparison Protection (Advanced Stage)
The stage can be used for directional comparison protection. This is set using the
Directional compar-
ison
parameter. With the
yes
setting, the function uses the threshold-value violation to determine the
direction (forward or reverse) and reports the indication
Direction
. The direction indicated is independent
of the directional mode set for the stage.
The
Release via input signal
setting and the
>Release delay & op.
input signal are available
with directional comparison protection. If the
Release via input signal
parameter is set to
yes
, the
start of the time delay, and therefore the tripping of the stage, are only enabled if the
>Release delay &
op.
input signal is active.
Method of Measurement (Basic and Advanced Stage)
You use the
Method of measurement
parameter to define whether the stage uses the
fundamental
comp.
or the calculated
RMS value
.
•
Measurement of the fundamental component:
This method of measurement processes the sampled current values and filters out the fundamental
component numerically.
•
Measurement of the RMS value:
This method of measurement determines the current amplitude from the sampled values according to
the defining equation of the RMS value. Harmonics are included in the analysis.
Dropout Delay (Advanced Stage)
If the value falls below the dropout threshold, the dropout can be delayed. The pickup is maintained for the
specified time. The tripping delay continues to run. If the time delay expires while the pickup is still main-
tained, the stage operates.
Blocking of the Stage (Basic and Advanced Stage)
The following blockings reset the picked up stage completely:
•
Externally or internally via the binary input signal
>Block stage
•
Measuring-voltage failure (see chapter
)
•
Via the dynamic settings function (only provided in the Advanced function type, see chapter Influence of
other functions via dynamic settings and chapter
)
Blocking of the Time Delay (Basic and Advanced Stage)
You can use the binary input signal
>Block delay & op.
to prevent the start of the time delay and thus
also the operate signal. A running time delay is reset. The pickup is indicated and the fault logging and
recording takes place.
Blocking of the Operate Delay and the Operate Signal via the Device-Internal Inrush-Current Detection Function
(Basic and Advanced Stage)
Blocking of the operate delay and the operate signal via the device-internal Inrush-current detection function
is described in chapter
Protection and Automation Functions
7.6 Directional Overcurrent Protection, Phases
SIPROTEC 5, High-Voltage Bay Controller, Manual
671
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...