With the
Activate device test mode
parameter, you activate the test mode that adds a test bit to the
output indications. If test mode is activated but the test mode of the relay outputs is not, no relay outputs are
activated by the protection functions.
Parameter: Oper.bin.outp. under test
•
Default setting
(_:151) Oper.bin.outp. under test
= inactive
If you activate the parameter
Oper.bin.outp. under test
, you can permit the closing of a binary output
for test purposes. In this way, indications are output during a device-wide test mode and the relays are either
activated or not. If an individual function is in test mode, only indications are output and the relays are not
activated.
i
i
NOTE
The device remains in test mode during every startup until you intentionally set the device back into
process mode. You set process mode by switching the parameterActivate device test mode to inactive
again (removing the check mark).
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Device
_:101
General:Rated frequency
•
50 Hz
•
60 Hz
50 Hz
_:102
General:Minimum
operate time
0.00 s to 60.00 s
0.00 s
_:138
General:Block moni-
toring dir.
•
off
•
on
off
Setting change
_:163
General:Reserv.time for
com.prot.
0 s to 65535 s
120 s
Spontan.indic.
_:139
General:Fault-display
•
with pickup
•
with trip
with pickup
Test support
_:150
General:Activate device
test mode
•
0
•
1
false
_:151
General:Oper.bin.outp.
under test
•
0
•
1
false
Information List
No.
Information
Data Class
(Type)
Type
General
_:510
General:>Test mode on
SPS
I
_:511
General:>Test mode off
SPS
I
_:507
General:>Device funct.logoff on
SPS
I
_:508
General:>Dev. funct.logoff off
SPS
I
_:512
General:>LED reset
SPS
I
_:52
General:Behavior
ENS
O
_:53
General:Health
ENS
O
_:51
General:Test mode
ENC
C
_:321
General:Protection on
SPC
C
3.10.2.3
3.10.2.4
System Functions
3.10 Device Settings
SIPROTEC 5, High-Voltage Bay Controller, Manual
167
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...