30°
-30°
Parameter:
Polarization with
•
Recommended setting value
(_:2311:104) Polarization with
=
zero sequence
This parameter is not available in the basic function. The basic function uses always zero-sequence compo-
nents for the direction determination.
You use the parameter
Polarization with
to select the values for the direction determination.
Parameter Value
Description
zero sequence
Select
zero sequence
to determine the direction via the zero-sequence
components V0 and 3I0.
Siemens recommends using the zero-sequence components for the direction
determination.
negative sequence
Select
negative sequence
to determine the direction via the negative-
sequence components V2 and I2.
The negative-sequence system can be used in case of danger that the zero-
sequence voltage is too small due to unfavorable zero-sequence impedance
conditions or that a parallel line influences the zero-sequence system.
Input Signal:
>Test of direction
If you activate the binary input signal
>Test of direction
, the direction is determined and indicated even
without the current threshold being exceeded in one of the stages. This provides an easy means of checking
the direction during commissioning, without changing the threshold values of the stages.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:2311:9
General:Measured value
•
3I0 calculated
•
IN measured
IN measured
_:2311:101
General:Min. voltage V0
or V2
0.150 V to 20.000 V
2.000 V
_:2311:102
General:Rotation angle
of ref. volt.
-180 ° to 180 °
-45 °
_:2311:103
General:Forward section
+/-
0 ° to 90 °
88 °
_:2311:104
General:Polarization
with
•
zero sequence
•
negative sequence
zero sequence
7.7.3.4
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual
707
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...