Stage
Setting Values
2
1.5 V
rated
0.1 s to 0.2 s
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Definite-T 1
_:181:1
Definite-T 1:Mode
•
off
•
on
•
test
off
_:181:2
Definite-T 1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:181:9
Definite-T 1:Measured
value
•
phase-to-ground
•
phase-to-phase
phase-to-phase
_:181:8
Definite-T 1:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:181:101
Definite-T 1:Pickup mode
•
1 out of 3
•
3 out of 3
1 out of 3
_:181:3
Definite-T 1:Threshold
0.300 V to 340.000 V
110.000 V
_:181:4
Definite-T 1:Dropout
ratio
0.90 to 0.99
0.95
_:181:6
Definite-T 1:Operate
delay
0.00 s to 300.00 s
3.00 s
Definite-T 2
_:182:1
Definite-T 2:Mode
•
off
•
on
•
test
off
_:182:2
Definite-T 2:Operate &
flt.rec. blocked
•
no
•
yes
no
_:182:9
Definite-T 2:Measured
value
•
phase-to-ground
•
phase-to-phase
phase-to-phase
_:182:8
Definite-T 2:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:182:101
Definite-T 2:Pickup mode
•
1 out of 3
•
3 out of 3
1 out of 3
_:182:3
Definite-T 2:Threshold
0.300 V to 340.000 V
130.000 V
_:182:4
Definite-T 2:Dropout
ratio
0.90 to 0.99
0.95
_:182:6
Definite-T 2:Operate
delay
0.00 s to 300.00 s
0.50 s
Information List
No.
Information
Data Class
(Type)
Type
Group indicat.
_:4501:55
Group indicat.:Pickup
ACD
O
_:4501:57
Group indicat.:Operate
ACT
O
Definite-T 1
_:181:81
Definite-T 1:>Block stage
SPS
I
7.13.5
7.13.6
Protection and Automation Functions
7.13 Overvoltage Protection with 3-Phase Voltage
SIPROTEC 5, High-Voltage Bay Controller, Manual
787
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...