Addr.
Parameter
C
Setting Options
Default Setting
_:18
Log.-inv.-T #:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:111
Log.-inv.-T #:Time dial
0.000 s to 60.000 s
1.250 s
Dyn.set: bin.input
_:34
Log.-inv.-T #:Effected by
binary input
•
no
•
yes
no
_:41
Log.-inv.-T #:Stage
blocked
•
no
•
yes
no
_:19
Log.-inv.-T #:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:112
Log.-inv.-T #:Time dial
0.000 s to 60.000 s
1.250 s
Information List
No.
Information
Data Class
(Type)
Type
Log.-inv.-T #
_:81
Log.-inv.-T #:>Block stage
I
_:501
Log.-inv.-T #:>Release delay & op.
I
_:84
Log.-inv.-T #:>Activ. dyn. settings
I
_:500
Log.-inv.-T #:>Block delay & op.
I
_:54
Log.-inv.-T #:Inactive
O
_:52
Log.-inv.-T #:Behavior
O
_:53
Log.-inv.-T #:Health
O
_:60
Log.-inv.-T #:Inrush blocks operate
O
_:62
Log.-inv.-T #:Dyn.set. AR cycle1act.
O
_:63
Log.-inv.-T #:Dyn.set. AR cycle2act.
O
_:64
Log.-inv.-T #:Dyn.set. AR cycle3act.
O
_:65
Log.-inv.-T #:Dyn.set. ARcycl.>3act
O
_:66
Log.-inv.-T #:Dyn.set. CLP active
O
_:67
Log.-inv.-T #:Dyn.set. BI active
O
_:68
Log.-inv.-T #:Dyn. set. blks. pickup
O
_:55
Log.-inv.-T #:Pickup
O
_:300
Log.-inv.-T #:Direction
O
_:56
Log.-inv.-T #:Operate delay expired
O
_:57
Log.-inv.-T #:Operate
O
7.7.7.4
Protection and Automation Functions
7.7 Directional Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual
735
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...