Addr.
Parameter
C
Setting Options
Default Setting
_:8341:18
Inverse-T 1:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A
7.50 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.500 A
5 A @ 50 Irated
0.15 A to 175.00 A
7.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.500 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
7.500 A
_:8341:106
Inverse-T 1:Time dial
0.05 to 15.00
1.00
Dyn.set: bin.input
_:8341:34
Inverse-T 1:Effected by
binary input
•
no
•
yes
no
_:8341:41
Inverse-T 1:Stage
blocked
•
no
•
yes
no
_:8341:19
Inverse-T 1:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.500 A
5 A @ 100 Irated 0.15 A to 175.00 A
7.50 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.500 A
5 A @ 50 Irated
0.15 A to 175.00 A
7.50 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.500 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
7.500 A
_:8341:107
Inverse-T 1:Time dial
0.05 to 15.00
1.00
Information List
No.
Information
Data Class
(Type)
Type
General
_:2311:500
General:>Activation emg. mode
SPS
I
_:2311:501
General:>Test of direction
SPS
I
_:2311:300
General:Emergency mode act.
SPS
O
_:2311:301
General:Test direction
ACD
O
Group indicat.
_:4501:55
Group indicat.:Pickup
ACD
O
_:4501:57
Group indicat.:Operate
ACT
O
Inverse-T 1
_:8161:81
Inverse-T 1:>Block stage
SPS
I
_:8161:501
Inverse-T 1:>Release delay & op.
SPS
I
_:8161:84
Inverse-T 1:>Activ. dyn. settings
SPS
I
_:8161:500
Inverse-T 1:>Block delay & op.
SPS
I
_:8161:54
Inverse-T 1:Inactive
SPS
O
_:8161:52
Inverse-T 1:Behavior
ENS
O
_:8161:53
Inverse-T 1:Health
ENS
O
_:8161:60
Inverse-T 1:Inrush blocks operate
ACT
O
_:8161:62
Inverse-T 1:Dyn.set. AR cycle1act.
SPS
O
_:8161:63
Inverse-T 1:Dyn.set. AR cycle2act.
SPS
O
_:8161:64
Inverse-T 1:Dyn.set. AR cycle3act.
SPS
O
_:8161:65
Inverse-T 1:Dyn.set. ARcycl.>3act
SPS
O
_:8161:66
Inverse-T 1:Dyn.set. CLP active
SPS
O
_:8161:67
Inverse-T 1:Dyn.set. BI active
SPS
O
_:8161:68
Inverse-T 1:Dyn. set. blks. pickup
SPS
O
7.6.5.4
Protection and Automation Functions
7.6 Directional Overcurrent Protection, Phases
688
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...