Figure 5-51
Connection of the Input Signal to the Control Circuit of the Circuit-Breaker Closing Coil
Every closure of the circuit breaker is recorded in the process. Therefore, detection is suppressed automatically
in the event of a close command by the internal AREC function of the device.
If external close commands are possible (actuation of the circuit breaker by other devices), which are not
intended to prompt detection of a manual closure (for example, with an external reclosing device), this can be
assured in 2 ways:
•
The input signal is connected in such a way that it is not activated in the event of external close
commands.
•
The external close command is connected to the blocking input
>Block manual close
for manual
closure detection.
Parameter: Action time
•
Recommended setting value
(_:6541:101) Action time
=
0.30 s
In order to ensure independence from manual activation of the input signal, the detection function is
extended for a defined length of time using the parameter
Action time
.
Siemens recommends an action time of
300 ms
.
Parameter: CB open dropout delay
•
Default setting
(_:102) CB open dropout delay
=
0 ms
With the
CB open dropout delay
parameter, you can maintain the effectiveness of the internal indication
CB open
for the set time. If the input signal
>Input
becomes active with a delay after an external close
command, the indication
(_:300) Detected
is issued as long as the dropout delay is effective (see
).
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Manual close
_:101
Manual close:Action
time
0.01 s to 60.00 s
0.30 s
_:102
Manual close:CB open
dropout delay
0.00 s to 60.00 s
0.00 s
Information List
No.
Information
Data Class
(Type)
Type
Manual close
_:501
Manual close:>Block manual close
SPS
I
_:500
Manual close:>Input
SPS
I
5.6.7.3
5.6.7.4
Function-Group Types
5.6 Function-Group Type Circuit Breaker, 1-/3-Pole
248
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...