Addr.
Parameter
C
Setting Options
Default Setting
_:12691:8
Inverse-T 1:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:12691:3
Inverse-T 1:Threshold
1 A @ 100 Irated 0.030 A to 35.000 A
1.200 A
5 A @ 100 Irated 0.15 A to 175.00 A
6.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
1.200 A
5 A @ 50 Irated
0.15 A to 175.00 A
6.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
1.200 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
6.000 A
_:12691:108
Inverse-T 1:Type of char-
acter. curve
_:12691:109
Inverse-T 1:Reset
•
instantaneous
•
disk emulation
disk emulation
_:12691:101
Inverse-T 1:Time dial
0.05 to 15.00
1.00
Information List
No.
Information
Data Class
(Type)
Type
Group indicat.
_:4501:55
Group indicat.:Pickup
ACD
O
_:4501:57
Group indicat.:Operate
ACT
O
Inverse-T 1
_:12691:81
Inverse-T 1:>Block stage
SPS
I
_:12691:500
Inverse-T 1:>Block delay & op.
SPS
I
_:12691:54
Inverse-T 1:Inactive
SPS
O
_:12691:52
Inverse-T 1:Behavior
ENS
O
_:12691:53
Inverse-T 1:Health
ENS
O
_:12691:60
Inverse-T 1:Inrush blocks operate
ACT
O
_:12691:59
Inverse-T 1:Disk emulation running
SPS
O
_:12691:55
Inverse-T 1:Pickup
ACD
O
_:12691:56
Inverse-T 1:Operate delay expired
ACT
O
_:12691:57
Inverse-T 1:Operate
ACT
O
Stage with User-Defined Characteristic Curve
Description
The User-defined characteristic curve overcurrent protection stage is only available in the advanced func-
tion type.
This stage is structured the same way as the stage with the inverse-time characteristic curve. The only differ-
ence is that you can define the characteristic curve as desired.
User-Defined Characteristic Curve
With the user-defined characteristic curve, you can define the operate curve point by point using up to 30
value pairs of current and time. The device uses linear interpolation to calculate the characteristic curve from
these values. You can also define a dropout characteristic curve if you wish.
Pickup and Dropout Behaviors with the User-Defined Characteristic Curve
When the input variable exceeds the threshold value by 1.1 times, the characteristic curve is processed.
7.8.4.4
7.8.5
7.8.5.1
Protection and Automation Functions
7.8 Overcurrent Protection, 1-Phase
SIPROTEC 5, High-Voltage Bay Controller, Manual
755
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...