Undervoltage Protection with 3-Phase Voltage
Setting Values for Stage Type Definite-Time Undervoltage Protection
Measured value
Phase-to-phase
Phase-to-ground
Method of measurement
Fundamental component
RMS value
Current-flow criterion
On
Off
Threshold value I>
1 A @ 50 and 100 Irated
0.030 A to 10.000 A
Increments of 0.001 A
5 A @ 50 and 100 Irated
0.15 A to 50.00 A
Increments of 0.01 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
Increments of 0.001 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
Increments of 0.001 A
Threshold value
75
0.300 V to 175.000 V
Increments of 0.001 V
Time delay
0.00 s to 60.00 s
Increments of 0.01 s
Dropout ratio
1.01 to 1.20
Increments of 0.01
Setting Values for Stage Type Inverse-Time Undervoltage Protection
Measured value
Phase-to-phase
Phase-to-ground
Method of measurement
Fundamental component
RMS value
Current-flow criterion
On
Off
Threshold value I>
1 A @ 50 and 100 Irated
0.030 A to 10.000 A
Increments of 0.001 A
5 A @ 50 and 100 Irated
0.15 A to 50.00 A
Increments of 0.01 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
Increments of 0.001 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
Increments of 0.001 A
Threshold
0.300 V to 175.000 V
Increments of 0.001 V
Pickup factor
0.80 to 1.00
Increments of 0.01
Characteristic constant k
0.00 to 300.00
Increments of 0.01
Characteristic constant α
0.010 to 5.000
Increments of 0.001
Characteristic constant c
0.000 to 5.000
Increments of 0.001
Time multiplier
0.05 to 15.00
Increments of 0.01
Additional time delay
0.00 s to 60.00 s
Increments of 0.01 s
Reset time
0.00 s to 60.00 s
Increments of 0.01 s
Operate Curve
T
op
=T
Inv
+T
add
Where:
T
op
Operate delay
T
Inv
Inverse-time delay
T
add
Additional time delay (parameter
Additional time delay
)
11.20
75
If you have selected the Method of measurement = RMS value, do not set the threshold value under 10 V.
Technical Data
11.20 Undervoltage Protection with 3-Phase Voltage
SIPROTEC 5, High-Voltage Bay Controller, Manual
1155
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...