Table 3-21
Description of Diagnostic Data of the COM Interface (Internal COM Link Interface Between
Module and Mainboard)
Protection Interfaces - Log
Type
Name
Values
Description - COM Interface
Layer Diagnostic Informa-
tion
(Internal COM Link Inter-
face in Mainboard Direc-
tion)
COM interface
RXHPFramesOK
Number of corresponding
frames (16 bit counter)
Incoming telegrams, high
priority, OK
COM interface
RXLPFramesOK
Number of corresponding
frames (16 bit counter)
Incoming telegrams, low
priority, OK
COM interface
RXHPFramesERR
Number of corresponding
frames (16 bit counter)
Incoming telegrams, high
priority, faulty
COM interface
RXLPFramesERR
Number of corresponding
frames (16 bit counter)
Incoming telegrams, low
priority, faulty
COM interface
TXHPFramesOK
Number of corresponding
frames (16 bit counter)
Sending telegrams, high
priority, OK
COM interface
TXLPFramesOK
Number of corresponding
frames (16 bit counter)
Sending telegrams, low
priority, OK
COM interface
TXHPFramesERR
Number of corresponding
frames (16 bit counter)
Sending telegrams, high
priority, faulty
COM interface
TXLPFramesERR
Number of corresponding
frames (16 bit counter)
Sending telegrams, low
priority, faulty
COM interface
Bridge Details Sub-nodes
Sub-nodes
Siemens-internal special
diagnostic for fault search
Table 3-22
Description of Diagnostic Data of some Setting Values of the Protection Interface
Protection Interfaces - Log
Type
Name
Values
Description - Protection
Interface Setting Values
Settings
Connection via
Integer number - display of
the internal coding of the
settings variant
Protection interface is
Connection via
Settings
PDI bandwidth
Bit-rate display
Bit rate (bit/s) for protection
telegrams based on the
parameter
Connection
via
Settings
PDI Telegram.Overhead
Display of bits
Overhead for every protec-
tion telegram in bit.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Device combin.
_:5131:102
Device combin.:Address of
device 1
1 to 65534
101
_:5131:103
Device combin.:Address of
device 2
1 to 65534
102
_:5131:104
Device combin.:Address of
device 3
1 to 65534
103
_:5131:105
Device combin.:Address of
device 4
1 to 65534
104
3.5.2.10
System Functions
3.5 Protection Communication
126
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...