Name Displayed in the DIGSI Function
Group Connections
Depending on the Connection Type, Name Transferred to the
PDC (in case it cannot be assigned automatically)
Measuring point I-3ph 1[ID 2]
MP-I3ph IA ID02
MP-I3ph IB ID02
MP-I3ph IC ID02
MP-I3ph I1 ID02
Measuring point I-1ph 1[ID 3]
MP-I1ph ID03
Measuring point U-1ph 1[ID 4]
MP-V1ph ID03
Table 9-6
Possible Binary Information Names
Path Displayed in DIGSI 5
(Can Be Edited)
Name Transferred to the PDC
(Cannot be Edited)
PMU 1:
Transf.bin.1:
>BinaryInfo.6
BIN-01-INFO-6
PMU 1:
Transf.bin.2:
>BinaryInfo.8
BIN-02-INFO-8
PMU 1:
Transf.bin.10:
>BinaryInfo.3
BIN-10-INFO-3
Data is transmitted continuously from the PMU to the PDC at the configured reporting rate. The transmission is
terminated by a corresponding trip command from the PDC or when the connection between the PDC and the
PMU is interrupted.
Communication between the PMU and the PDC can be passed via TCP or UDP protocols.
The following ports are used for data transmission:
•
TCP: Port 4712
•
UDP: Port 4713
The ports must be configured on the PDC.
If you are using the UDP protocol for communication between the PMU and the PDC, you can set either
command mode
or
asynchronous response mode
as the
communication mode
. In
asynchronous
response mode
, data can be transmitted continuously to preset PDC destination addresses in IEEE C37.118
format without a PDC having to request transmission of the synchrophasor data via a close command to the
PMU.
Up to 3 different PDCs can be connected to one device PMU at the same time. The IP addresses of the
maximum 3 PDCs are set in the PMU function group. If 4 device PMUs are configured, this enables support for
up to 12 PDCs.
Parameterizing the PMU with DIGSI
You configure and parameterize the Phasor Measurement Unit with DIGSI. After a device has been added in a
DIGSI project, one or more communication modules that support synchrophasors can be configured as PMUs.
The device module supports a maximum of 2 communication modules that can be configured as PMUs. If
more than 2 PMUs are needed, the device must be expanded with a CB202 plug-in module assembly (expan-
sion module), which can accommodate 2 more communication modules.
The following communication modules support synchrophasors:
•
ETH-BA-2EL (2 x Ethernet electric, RJ45)
•
ETH-BB-2FO ( 2 x Ethernet optical, 2 km, LC duplex)
9.5.6
Measured Values, Energy Values, and Supervision of the Primary System
9.5 Phasor Measurement Unit (PMU)
1006
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...