Addr.
Parameter
C
Setting Options
Default Setting
_:14011:147
90V V.contr.2w:VT
supervision threshold
0.5 % to 10.0 %
10.0 %
_:14011:148
90V V.contr.2w:VT
supervision time delay
1 s to 600 s
10 s
_:14011:149
90V V.contr.2w:Circul.
current blocking
•
off
•
on
on
_:14011:150
90V V.contr.2w:Circul.
current threshold
10 % to 500 %
50 %
_:14011:151
90V V.contr.2w:Circul.
current time delay
0 s to 1000 s
60 s
Line drop comp.
_:14011:125
90V V.contr.2w:Line
drop compensation
•
off
•
LDC-Z
•
LDC-XandR
off
_:14011:126
90V V.contr.2w:Target
voltage rising
0.0 % to 20.0 %
4.0 %
_:14011:127
90V V.contr.2w:Max
load current
0.0 % to 500.0 %
100.0 %
_:14011:153
90V V.contr.2w:R line
0.00 Ω to 30.00 Ω
0.00 Ω
_:14011:154
90V V.contr.2w:X line
-30.00 Ω to 30.00 Ω
0.00 Ω
Limiting
_:14011:102
90V V.contr.2w:Lower
tap-position limit
-128 to 127
1
_:14011:103
90V V.contr.2w:Higher
tap-position limit
-128 to 127
15
_:14011:128
90V V.contr.2w:Vmin
limiting
•
off
•
on
on
_:14011:129
90V V.contr.2w:Vmin
threshold
10.000 V to 340.000 V
105.000 V
_:14011:130
90V V.contr.2w:Vmin
time delay
0 s to 20 s
10 s
_:14011:131
90V V.contr.2w:Vmax
limiting
•
off
•
on
on
_:14011:132
90V V.contr.2w:Vmax
threshold
10.000 V to 340.000 V
115.000 V
_:14011:133
90V V.contr.2w:Vmax
time delay
0 s to 20 s
10 s
Blocking
_:14011:134
90V V.contr.2w:Blocking
behavior
•
Auto
•
Auto-Manual
Auto-Manual
_:14011:135
90V V.contr.2w:V<
Blocking
•
off
•
on
on
_:14011:136
90V V.contr.2w:V<
Threshold
10.000 V to 340.000 V
90.000 V
_:14011:137
90V V.contr.2w:V< Time
delay
0 s to 20 s
0 s
_:14011:138
90V V.contr.2w:I>
Blocking
•
off
•
on
on
_:14011:139
90V V.contr.2w:I>
Threshold
10 % to 500 %
150 %
Control Functions
6.9 Voltage Controller
SIPROTEC 5, High-Voltage Bay Controller, Manual
503
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...