[lohyster-010415-01.vsd, 1, en_US]
If the Synchronization function is started within the hysteresis, no switching is performed as a result of the
minimum and maximum operating limit (parameters
Min. operating limit Vmin
and
Max. operat.
limit Vmax
). If the Synchronization function is started within the voltage operating range and the voltage
exceeds the minimum or maximum operating limit during the synchronization process, selecting can occur in
the area of the hysteresis.
Parameter:
Max.durat. sync.process
•
Default setting
(_:5071:110) Max.durat. sync.process
=
30 s
The parameterized conditions must be fulfilled within this time. If the conditions are not fulfilled, no further
closing release takes place and the synchronization stage is stopped. If this time is set to ∞, the conditions are
checked until they are fulfilled. This is also the default setting. Observe the operating conditions when
defining the time limitation. This must be defined specifically for each system. If 0 or 0.01 s is set, then all
conditions are checked once at the starting time point. Thereafter the process is stopped immediately.
Parameter:
Voltage adjustment
•
Default setting
(_:5071:126) Voltage adjustment
=
1.00
The parameter can be used for correction of amplitude errors, for example, due to indirect measurement (for
example, tap changer).
To apply a transformer between measuring points, the
Voltage adjustment
parameter is not needed. The
transformer ratios are set for the measuring points and the function will take them into account automatically.
Parameter:
Angle adjust. (transform.)
•
Default setting
(_:2311:127) Angle adjust. (transform.)
=
0
o
The parameter can be applied under the following conditions:
•
1. Phase-angle rotation by power transformer between the measuring points
•
2. Correction of phase-angle errors
1. Phase-angle rotation by power transformer between the measuring points:
Control Functions
6.4 Synchronization Function
370
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...