Addr.
Parameter
C
Setting Options
Default Setting
_:2311:136
General:Op. mode
BFP
•
unbalancing
•
I> query
unbalancing
Trip logic
_:5341:101
Trip logic:Trip at
2ph short circuit
•
3-pole
•
1-pole, leading phase
•
1-pole, lagging phase
3-pole
_:5341:102
Trip logic:3-pole
coupling
•
with pickup
•
with trip
with trip
_:5341:103
Trip logic:Reset of
trip command
•
with I<
•
with I< & aux.contact
•
with dropout
with I<
Circuit break.
_:4261:101
Circuit
break.:Output time
0.02 s to 1800.00 s
0.10 s
_:4261:105
Circuit
break.:Indicat. of
breaking values
•
with trip
•
always
always
Manual close
_:6541:101
Manual
close:Action time
0.01 s to 60.00 s
0.30 s
_:6541:102
Manual close:CB
open dropout delay
0.00 s to 60.00 s
0.00 s
Control
_:4201:101
Control:Control
model
•
status only
•
direct w. normal secur.
•
SBO w. normal secur.
•
direct w. enh. security
•
SBO w. enh. security
SBO w. enh.
security
_:4201:102
Control:SBO time-
out
0.01 s to 1800.00 s
30.00 s
_:4201:103
Control:Feedback
monitoring time
0.01 s to 1800.00 s
1.00 s
_:4201:104
Control:Check
switching authority
•
no
•
yes
•
advanced
yes
_:4201:105
Control:Check if
pos. is reached
•
no
•
yes
yes
_:4201:106
Control:Check
double activat. blk.
•
no
•
yes
yes
_:4201:107
Control:Check blk.
by protection
•
no
•
yes
yes
Switching authority
_:4201:151
Control:Swi.dev.
related sw.auth.
•
0
•
1
false
_:4201:152
Control:Specific sw.
authorities
•
0
•
1
true
_:4201:115
Control:Specific
sw.auth. valid for
•
station
•
station/remote
•
remote
station/remote
_:4201:153
Control:Num. of
specific sw.auth.
2 to 5
2
Control Functions
6.2 Switching Devices
322
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...