Error parameters are displayed to you by inconsistency indications in DIGSI.
Application and Setting Notes
Parameter (General):
Mode
•
Default setting
(_:1) Mode
=
on
With the
Mode
parameter, you specify whether you want to activate, deactivate, or test the supervision of the
signaling voltage for the appropriate group. If you put the group into test mode, the
Sig. volt.
disturbed
indication is given a test flag. If the supervision input drops out in test mode, the assigned inputs
retain their status without their quality attribute being set to invalid.
Parameter (Supervision Signal):
I/O module ID
•
Default setting
(_:104) I/O module ID
=
I/O module 1
Using the
I/O module ID
parameter, you specify the I/O module for which you want to activate signaling-
voltage supervision. Counting of the I/O modules starts in increasing order with the binary inputs of the base
module. The binary inputs of the PS201 power-supply module permanently installed in the base module count
as the 2nd I/O module followed by additional I/O modules (3 to n) in the expansion boards of the device.
Parameter (Supervision Signal):
Binary input
•
Default setting
(_:105) Binary input
=
1
Using the
Binary input
parameter, you specify the binary input responsible for the supervision of the
signaling voltage for the parameterized I/O module. The quality attribute of all other binary inputs for this
module are set to valid or invalid depending on the presence of the signaling voltage at the parameterized
binary input.
Parameter (Supervision Signal):
Enable variable group
•
Default setting
(_:102) Enable variable group
=
untrue
You can activate the parameter
Enable variable group
by placing the check mark. If you have not set
the check mark (default setting), only these 2 parameters are available for the configuration of the supervision
signal. If you have set the check mark, the parameter menu is extended by the areas Start supervision group
and End supervision group. You can then use that to carry out the grouping of binary inputs for supervision
groups explained in the function description.
Parameter (Start Supervision Group):
I/O module ID
•
Default setting
(_:106) I/O module ID
=
I/O module 1
Parameter
I/O module ID
is used to define the first I/O module that you want to assign to a supervision
group. As the counting of the I/O module starts in ascending order with the binary inputs of the base module,
this is the module with the lowest counter number that you can use for carrying out a grouping.
Parameter (Start Supervision Group):
Binary input
•
Default setting
(_:107) Binary input
=
1
Parameter
Binary input
is used to define the lowest binary input for the first I/O module (see
(_:106)
I/O module ID
) that you want to assign to a supervision group.
Parameter (End Supervision Group):
I/O module ID
•
Default setting
(_:108) I/O module ID
=
I/O module 1
Parameter
I/O module ID
is used to define the last I/O module that you want to assign to a supervision
group. As the counting of the I/O module starts in ascending order with the binary inputs of the base module,
this is the module with the highest counter number that you can use for carrying out a grouping.
8.3.3.4
Supervision Functions
8.3 Supervision of the Secondary System
948
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...