NOTE
If you would like to avoid automatic reclosing during individual short-circuit types, please set the respective
dead times to
oo (invalid)
.
Example:
After 1-phase short-circuits, the automatic reclosing function should occur after 1.2 s. The automatic reclosing
function should not occur for 2-phase and 3-phase short circuits.
For this application, the parameters should be set as follows:
•
Dead time aft.1ph. pickup
=
1.2 s
•
Dead time aft.2ph. pickup
=
oo (invalid)
•
Dead time aft.3ph. pickup
=
oo (invalid)
Parameter: Dead time aft. evolv. fault
These parameters are only significant if the parameter
(_:6601:109) Response to evolv. faults
is
set to
strt. evol.flt.dead time
.
•
Default setting
(_:6571:109) Dead time aft. evolv. fault
=
1.2 s
With the parameter
Dead time aft. evolv. fault
, you can determine after which dead time the auto-
matic reclosing function should be executed, if based on an evolving fault during the current dead time, a 3-
pole trip has occurred. For this 3-pole dead time, stability concerns for the system are also important. Often,
this dead time as well as the parameter
(_:6571:108) Dead time aft. 3-pole trip
can be set.
Detailed information about the function during evolving faults during dead time are described in Chapter
7.2.4.13 Evolving-Fault Detection During Dead Time
Parameter: CB ready check bef.close
•
Default setting
(_:6571:111) CB ready check bef.close
=
no
With the parameter
CB ready check bef.close
you can determine if after the expiration of the dead
time (meaning, directly prior to assigning the close command) readiness of the circuit breaker should be
queried.
Parameter Value
Description
no
With the setting
no
, the automatic reclosing function does not check again
the readiness of the circuit breaker prior to assigning the close demand.
Siemens recommends this setting, if it is sufficient to check the readiness of the
circuit breaker for the entire switching cycle once before the start of a reclosing
function, consisting of tripping-reclosing-tripping. The setting for checking the
readiness of the circuit breaker prior to the start of the automatic reclosing
function is done using the parameter
(_:6601:102) CB ready check
bef. start
.
yes
With the setting
yes
, the dead time can be extended if after the expiration of
the dead time the circuit breaker is not ready for the next ON-OFF cycle. The
maximum delay of the dead time can be set with the parameter
(_:
6601:111) Max. dead-time extension
.
Siemens recommends this setting, if it can be assumed that the circuit breaker
becomes available to switch on the reclosing function only after an additional
waiting period.
Detailed information about the function can be found in Chapters
7.2.4.16 Circuit-Breaker Readiness and
and
7.2.4.14 Closing Indication and Close Command
.
Parameter: Synchroch. aft. 3-pole d.t.
•
Default setting
(_:6571:110) Synchroch. aft. 3-pole d.t.
=
none
Protection and Automation Functions
7.2 Automatic Reclosing Function
SIPROTEC 5, High-Voltage Bay Controller, Manual
593
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...