Group Indications
The following group indications are available:
•
(_:300) Group alarm
•
(_:301) Group warning
•
(_:302) Group indication
You can find the signals in the DIGSI 5 project tree under Name of the device) → Information routing. In the
operating range, you can find the signals under Alarm handling (see the following figure).
[scgrwarn-010313-01, 1, en_US]
Figure 8-37
Group Monitoring Indication in the DIGSI 5 Information Routing Matrix
Alarm Handling Group Alarm
The indication
(_:300) Group alarm
is the group indication for defect-severity 4 monitoring. This moni-
toring has a special purpose, as it is set user-specifically by a binary input signal and not by internal device
supervision. Nevertheless, the response of the device is serious, such as for example the blocking of all protec-
tion and automatic functions (see chapter
8.8.5 Defect Severity 4 (Group Alarm)
).
If the binary input signal
(_:503) >Group Alarm
is set, the group indication
(_:300) Group alarm
becomes active. If the binary input signal
(_:503) >Group Alarm
is reset, the signal
(_:300) Group
alarm
is also reset and the device returns to the normal operating state.
In the delivery condition, every device has the CFC chart Process mode inactive that initiates the
>Group
Alarm
. This CFC chart checks whether the device is still accidentally in the simulation or commissioning
mode.
You can adapt the CFC chart as needed. You can find the CFC chart in the DIGSI 5 project tree under Name of
the device → Charts.
Alarm Handling Group Warning
The indication
(_:301) Group warning
is the group indication for defect-severity 1 monitoring. Some
error messages of defect severity 1 are firmly linked to the signal
(_:301) Group warning
, others are
connected in a flexible way via a CFC chart in the device delivery condition. This allocation is described in
chapter
.
In the delivery condition, every device has the CFC chart Group warning, that initiates the
Group warning
.
You can adapt the CFC chart as needed. You can find the CFC chart in the DIGSI 5 project tree under Name of
the device → Charts.
8.9
Supervision Functions
8.9 Group Indications
SIPROTEC 5, High-Voltage Bay Controller, Manual
991
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...