EXAMPLE of Placeholder Characters:
Example 1:
•
binary 00000000.00000000.00000000.00101011 is not permitted
•
binary 00000000.00000000.00000000.00111111 is permitted
Example 2:
•
The PDC IP address is: 192.172.16.1
•
Placeholder: 0.0.0.127
The device accepts requests within the IP address range of 192.172.16.1 to 192.172.16.127.
Example 3:
•
The PDC IP address is: 192.172.16.100
•
Placeholder: 0.0.0.3
The device accepts requests within the IP address range of 192.172.16.100 to 192.172.16.103.
If a PDC attempts to establish a connection to the device, the PDC IP addresses and corresponding place-
holders are checked in the same order as they had been configured (IP address PDC1, IP address PDC2,
IP address PDC3). Running through the list is stopped with the first match of the IP address, placeholder and
requested IP address range and the connection is built-up. If there are no matches, the attempt to connect is
rejected.
If you have configured IP address 0.0.0.0 and the placeholder 255.255.255.255, every IP address received is
accepted as valid. This could be of use in the course of commissioning measures.
i
i
NOTE
You must have configured at least 1 IP address in order to establish a connection between the device and
PDC.
If you use the asynchronous data transmission method, set the
PMU transfer
parameter to
UDP
and the
Communication mode
parameter to
Spontaneous operation
. The PMU data are then sent cyclically via
UDP to each PDC/IP address permanently configured in DIGSI. You may not configure placeholders for PDC/IP-
address ranges in this communication mode.
Data output starts immediately after the device has booted. In this way, no starting signal from the PDC is
necessary to start data transmission.
[sc_spontan_pmu, 1, en_US]
Figure 9-11
PMU Configuration for Spontaneous Transmission
Measured Values, Energy Values, and Supervision of the Primary System
9.5 Phasor Measurement Unit (PMU)
1010
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...