Application and Setting Notes
Parameter:
Threshold
•
Recommended setting value
(_:1981:3) Threshold
=
10 %
The setting of the parameter
Threshold
depends on the respective application. A threshold value of 10 % is
a practicable value for fault indications of electrical machines.
Parameter:
Operate delay
•
Recommended setting value
(_:1981:6) Operate delay
=
1500 ms
The setting of the
Operate delay
depends on the application. Observe the time grading in the power-
system protection and do not set the time for monitoring too short. The default setting is practicable. For
motors, the time depends on the permissible time period for the set unbalanced load.
Parameter:
Blk. w. inrush curr. detect.
•
Default setting
(_:1981:104) Blk. w. inrush curr. detect.
=
no
With the parameter
Blk. w. inrush curr. detect.
, the stage can be stabilized against tripping on
transformer-inrush currents. If transformers are parts of the protection zones, set this parameter to
yes
.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
General
_:2311:106
General:Reference value
•
pos. seq. current
•
rated current
rated current
_:2311:107
General:Current limita-
tion Imax
•
no
•
yes
no
_:2311:101
General:Maximum phase
current
1 A @ 100 Irated 0.030 A to 35.000 A
10.000 A
5 A @ 100 Irated 0.15 A to 175.00 A
50.00 A
1 A @ 50 Irated
0.030 A to 35.000 A
10.000 A
5 A @ 50 Irated
0.15 A to 175.00 A
50.00 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
10.000 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
50.000 A
_:2311:104
General:Release current 1 A @ 100 Irated 0.030 A to 10.000 A
0.050 A
5 A @ 100 Irated 0.15 A to 50.00 A
0.25 A
1 A @ 50 Irated
0.030 A to 10.000 A
0.050 A
5 A @ 50 Irated
0.15 A to 50.00 A
0.25 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
0.050 A
5 A @ 1.6 Irated
0.005 A to 8.000 A
0.250 A
Definite-T 1
_:1981:1
Definite-T 1:Mode
•
off
•
on
•
test
off
_:1981:2
Definite-T 1:Operate &
flt.rec. blocked
•
no
•
yes
no
_:1981:3
Definite-T 1:Threshold
5.0 % to 999.9 %
10.0 %
_:1981:4
Definite-T 1:Dropout
ratio
0.40 to 0.99
0.95
_:1981:104
Definite-T 1:Blk. w.
inrush curr. detect.
•
no
•
yes
no
7.25.4
7.25.5
Protection and Automation Functions
7.25 Negative-Sequence Protection
SIPROTEC 5, High-Voltage Bay Controller, Manual
873
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...