Figure 6-75
Operating Range Under Synchronous and Asynchronous Conditions for Voltage (V) and
Frequency (f)
Application and Setting Notes
Parameter:
Synchronous operating mode
,
Asynchronous operating mode
•
Default setting
(_:5041:119) Sync. operating mode
=
off
•
Default setting
(_:5041:114) Async. operating mode
=
off
The operating modes of the stages can be activated or deactivated via the parameters. The operating modes
are deactivated in the default setting for safety reasons.
The following combination options are possible:
Sync. operating mode
Async. operating mode
Description
on
on
If the frequency difference is below the threshold
value set
f-threshold ASYN<->SYN
, the oper-
ating mode synchronous is active. In other cases, the
operating mode asynchronous is active.
If you wish to interconnect galvanically isolated
systems, then select this operating mode.
6.4.8.2
Control Functions
6.4 Synchronization Function
384
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...