[lolsuebe-010611-01.tif, 1, en_US]
Figure 7-50
Cyclic Reclosing Function: Logic for Circuit-Breaker Condition and Supervision
Blockings
The Automatic reclosing function differentiates between 2 types of blockings, see
:
•
Static blocking
•
Dynamic blocking
Static Blocking
The Automatic reclosing function is statically blocked if the function is switched on, but is not ready for
reclosing and also cannot be started as long as this blocking is present. The dynamic blocking is signaled with
the indication
Inactive
.
The following conditions lead to the static blocking:
Condition
Indication
Manual closing of the circuit breaker, recognition through binary
input or internal device control.
The blocking is temporary, the duration can be set with the
parameter
Block. time aft. man.close
.
Inactive
Circuit breaker not available for automatic reclosing function,
recognition through binary input. This cause can be switched on
or off through the parameter
CB ready check bef.close
.
Inactive
Circuit breaker of non-closed 3-pole, recognition through binary
input.
This criteria is used if the circuit-breaker auxiliary contacts are
connected.
Inactive
7.2.4.17
Protection and Automation Functions
7.2 Automatic Reclosing Function
SIPROTEC 5, High-Voltage Bay Controller, Manual
571
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...