Pickup Mode
The
Pickup mode
parameter defines whether the protection stage picks up if all 3 measuring elements
detect the overvoltage condition (
3 out of 3
) or if only 1 measuring element detects the overvoltage
condition (
1 out of 3
).
Measured Value
Use the
Measured value
parameter to define whether the tripping stage analyzes the phase-to-phase
voltages V
AB
, V
BC
, and V
CA
, or the phase-to-ground voltages V
A
, V
B
, and V
C
.
If the measured value is set to phase-to-phase, the function reports those measuring elements that have
picked up.
Blocking the Stage
In the event of blocking, the picked up stage will be reset. Blocking is possible externally or internally via the
binary input signal
>Block stage
.
Application and Setting Notes
Parameter:
Method of measurement
•
Recommended setting value
(_:181:8) Method of measurement
=
fundamental comp.
With the
Method of measurement
parameter, you define whether the stage uses the fundamental
component (standard method = default setting) or the calculated RMS value.
Parameter Value
Description
fundamental comp.
Select this method of measurement to suppress harmonics or transient
voltage peaks.
Siemens recommends this method of measurement as the default setting.
RMS value
Select this method of measurement if you want the stage to take harmonics
into account (for example, at capacitor banks). Do not set the threshold
value of the stage under 10 V for this method of measurement.
Parameter:
Measured value
•
Default setting
(_:181:9) Measured value
=
phase-to-phase
With the
Measured value
parameter, you define whether the stage monitors the phase-to-phase voltages
V
AB
, V
BC
, and V
CA
or the phase-to-ground voltages V
A
, V
B
, and V
C
.
Parameter Value
Description
phase-to-phase
If you want to monitor the voltage range, keep
phase-to-phase
as the
default setting. In this case, the function will not pick up on ground faults.
Siemens recommends the measured value
phase-to-phase
as the
default setting.
phase-to-ground
Select the
phase-to-ground
setting if you want to detect voltage unbal-
ances and overvoltage conditions caused by ground faults.
Parameter:
Threshold
•
Default setting
(_:181:3) Threshold
=
110 V
Depending on the
Measured value
, the
Threshold
is set either as phase-to-phase quantity or as phase-
to-ground quantity. The default setting assumes that the voltage range is monitored on long-distance trans-
mission lines under low-load conditions.
Specify the
Threshold
(pickup threshold) for the specific application.
7.13.4
Protection and Automation Functions
7.13 Overvoltage Protection with 3-Phase Voltage
SIPROTEC 5, High-Voltage Bay Controller, Manual
785
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...