With the
Additional time delay
parameter, you define a definite-time delay in addition to the inverse-
time delay.
If the setting is left on its default value of 0 s, only the inverse-time delay is operative.
Parameter:
Reset time
•
Default setting
(_:107) Reset time
=
0.00 s
With the
Reset time
parameter, you define the reset time delay which is started when the voltage falls
below the dropout threshold. Set the parameter
Reset time
to 0 s when instantaneous reset is desired.
Under network conditions of intermittent faults or faults which occur in rapid succession, Siemens recom-
mends setting the
Reset time
to an appropriate value (> 0 s) to ensure the operation. Otherwise Siemens
recommends to keep the default value to ensure a fast reset of the function.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Inverse-T #
_:1
Inverse-T #:Mode
•
off
•
on
•
test
off
_:2
Inverse-T #:Operate &
flt.rec. blocked
•
no
•
yes
no
_:9
Inverse-T #:Measured
value
•
phase-to-ground
•
phase-to-phase
phase-to-phase
_:8
Inverse-T #:Method of
measurement
•
fundamental comp.
•
RMS value
fundamental
comp.
_:108
Inverse-T #:Pickup mode
•
1 out of 3
•
3 out of 3
1 out of 3
_:3
Inverse-T #:Threshold
0.300 V to 340.000 V
110.000 V
_:101
Inverse-T #:Pickup factor
1.00 to 1.20
1.10
_:102
Inverse-T #:Charact.
constant k
0.00 to 300.00
1.00
_:103
Inverse-T #:Charact.
constant α
0.010 to 5.000
1.000
_:104
Inverse-T #:Charact.
constant c
0.000 to 5.000
0.000
_:105
Inverse-T #:Time dial
0.05 to 15.00
1.00
_:106
Inverse-T #:Additional
time delay
0.00 s to 60.00 s
0.00 s
_:107
Inverse-T #:Reset time
0.00 s to 60.00 s
0.00 s
Information List
No.
Information
Data Class
(Type)
Type
Inverse-T #
_:81
Inverse-T #:>Block stage
SPS
I
_:54
Inverse-T #:Inactive
SPS
O
_:52
Inverse-T #:Behavior
ENS
O
_:53
Inverse-T #:Health
ENS
O
_:55
Inverse-T #:Pickup
ACD
O
7.13.9
7.13.10
Protection and Automation Functions
7.13 Overvoltage Protection with 3-Phase Voltage
SIPROTEC 5, High-Voltage Bay Controller, Manual
793
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...