[dwtcs1be-110611-01.tif, 2, en_US]
Figure 8-30
Principle of Trip-Circuit Supervision with 1 Binary Input
CR
Command relay
CB
Circuit breaker (closed)
CB coil
Circuit-breaker coil
AuxCon1
Circuit-breaker auxiliary contact (closed when CB is closed)
AuxCon2
Circuit-breaker auxiliary contact (open when CB is closed)
V-Ctrl
Control voltage (tripping voltage)
V-BI
Input voltage for binary input
R
Equivalent resistance
The supervision with 1 binary input identifies disruptions in the trip circuit and the failure of the control
voltage.
In normal operation, the binary input is activated with the command relay open and the trip circuit intact (H).
The supervision circuit is closed with the equivalent resistance R or with the auxiliary contact AuxCon1 of the
closed circuit breaker. The binary input is not activated while the command relay is closed (L). If the binary
input is not activated for a prolonged time, there is a disruption in the trip circuit or the control voltage has
failed.
No
.
Command
Relay
CB
AuxCon1
AuxCon2
BI
Dynamic State
Static State
1
Open
ON
Closed
Open
H
Normal operation with closed circuit breaker
2
Open
OFF
Open
Closed
H
Normal operation with open circuit breaker
3
Closed
ON
Closed
Open
L
Transmission or fault
Fault
4
Closed
OFF
Open
Closed
L
CR successfully activated the circuit breaker
Use the parameter
Blk.by trip/open cmd from
to set the conditions under which the trip-circuit super-
vision is blocked. The following conditions can cause a blocking of the trip-circuit supervision function:
•
The
Trip/open cmd.
of the circuit breaker is activated.
•
One of the trip commands of the circuit-breaker failure protection is activated.
As long as the trip-circuit supervision function is blocked, the closed contact of the command relay does not
cause a failure indication.
If the command contacts of other devices work in parallel on the trip circuit, the failure indication must be
delayed. With the
Alarm delay
parameter, you can set the time delay. After fixing the fault in the trip
circuit, the failure indication will automatically expire after the same time.
Supervision Functions
8.3 Supervision of the Secondary System
SIPROTEC 5, High-Voltage Bay Controller, Manual
971
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...