Underfrequency Load Shedding
Setting Values for the Function
Minimum voltage
0.300 p.u. to 0.900 p.u.
Increments of 0.001 p.u.
Minimum current
0.020 p.u. to 0.200 p.u.
Increments of 0.001 p.u.
Power angle
-30° to 30°
Increments of 1°
Positive power direction
inv. to CT neu.pnt sett.
acc. to CT neu.pnt sett.
Threshold value for the df/dt-rising
rate or df/dt-falling rate
0.1 Hz/s to 20.0 Hz/s
Increments of 0.1 Hz/s
df/dt measuring window
2 periods to 5 periods
Increments of 1 period
df/dt dropout differential
0.02 Hz/s to 0.99 Hz/s
Increments of 0.10 Hz/s
f < stabilization counter
1 to 20
Increments of 1
Setting Values for the Stage
Pickup threshold
40.00 Hz to 70.00 Hz
Increments of 0.01 Hz
Dropout differential
20 mHz to 2000 mHz
Increments of 10 mHz
Time delay
0.00 s to 60.00 s
Increments of 0.01 s
Times
Pickup times with stabilization counter = 6
Approx. 85 ms + OOT
81
at 50 Hz
Approx. 80 ms + OOT at 60 Hz
Dropout time
Approx. 80 ms + OOT at 50 Hz
Approx. 75 ms + OOT at 60 Hz
Dropout
The greater dropout differential (=
| pickup value – dropout value |
) of the following 2 criteria
applies:
Dropout
Frequency
0.01 Hz
df/dt-rising rate and df/dt-falling rate
0.1 Hz/s
Voltage V1
105 % of the threshold value
Current I1
105 % of the threshold value at φ ≤ 0
95.23 % of the threshold value at φ > 0
Power angle
1°
Minimum absolute dropout differential
Protection-class current transformer
15 mA sec. (I
rated
= 1 A) or
75 mA sec. (I
rated
= 5 A)
Instrument current transformer
0.5 mA sec. (I
rated
= 1 A) or
2.5 mA sec. (I
rated
= 5 A)
Voltage transformer
150 mV sec.
Tolerances
Frequency f<
f
rated
- 0.20 Hz < f < f
rated
+ 0.20 Hz
± 5 mHz at V = V
rated
11.24
81
OOT (Output Operating Time): additional time delay of the output medium used, for example, 5 ms with fast relay
Technical Data
11.24 Underfrequency Load Shedding
SIPROTEC 5, High-Voltage Bay Controller, Manual
1161
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...