Parameter Value
Description
yes
The automatic reclosing function checks the readiness of the circuit breaker for
a switching cycle, consisting of a tripping-reclosing-switching.
If the circuit breaker is ready - signaled through a binary input - the startup of
the automatic reclosing function can occur. If the circuit breaker is not ready,
the automatic reclosing function reports the static blocking.
Siemens recommends using this setting.
Note: The presetting of this parameter does not correspond with the recom-
mended setting for operation. The automatic reclosing function would other-
wise be blocked with a non-available circuit breaker-ready-signal. Please set the
parameter as recommended.
no
The readiness of the circuit breaker is not checked before starting the automatic
reclosing function. The test also does not occur if the readiness signal from the
circuit breaker is connected to a binary input on the device.
Parameter: Reclai. time aft.succ.cyc.
•
Default setting
(_:6601:103) Reclai. time aft.succ.cyc.
=
3.00 s
With the
Reclai. time aft.succ.cyc.
parameter, set the time used to decide if the currently running
reclosing cycle was successful or not. Detailed information about the function of the reclaim time can be
found in the chapter
The presetting for the reclaim time can be frequently maintained. In regions where thunderstorms and storms
often occur, a shorter reclaim time makes sense in order to minimize the danger of the final disconnection due
to sequential lightning strikes or cable spark over.
Select a long reclaim time if there is no possibility for circuit-breaker supervision with multiple automatic
reclosing, for example, due to missing auxiliary contacts or lacking circuit-breaker-ready-information. In this
case, the reclaim time must be longer than the recovery time of the circuit breaker.
Parameter: Block. time aft. man.close
•
Default setting
(_:6601:104) Block. time aft. man.close
=
1.00 s
With the
Block. time aft. man.close
parameter, the time is determined for which the automatic
reclosing should be blocked after a manual connection.
Set the time so that the circuit breaker can be safely switched on and off during connection to a short circuit
without the automatic reclosing function being automatically closed.
Parameter: Start signal supervis.time
•
Default setting
(_:6601:105) Start signal supervis.time
=
0.25 s
With the
Start signal supervis.time
parameter, set the maximum time after which a circuit breaker
must be opened after a trip command. If the time expires, a failure of the circuit breaker is assumed and the
automatic reclosing function is dynamically blocked.
Detailed information about the function of the start supervision time can be found in the chapter
Protection and Automation Functions
7.2 Automatic Reclosing Function
SIPROTEC 5, High-Voltage Bay Controller, Manual
587
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...