In this example, the pickup and operate indications of the protection functions are exchanged in the direction
of the Circuit-breaker function group.
You must connect the Voltage 3-phase function group with the Circuit-breaker function group. This assign-
ment can be made in DIGSI only via Project tree → Connect function group. To connect the interfaces, set a
cross at the intersection between the row and column in the matrix.
[sc3span2-190214-01, 1, en_US]
Figure 5-15
Connecting Voltage 3-Phase Function Group with Circuit-Breaker Function Group
Operational Measured Values
The operational measured values are always present in the Voltage 3-phase function group and cannot be
deleted.
The following table shows the operational measured values of the Voltage 3-phase function group:
Table 5-4
Operational Measured Values of the Voltage 3-Phase Function Group
Measured Values
Primary Secon-
dary
% Referenced to
V
A
, V
B
, V
C
Phase-to-ground voltages
kV
V
Operating rated voltage of primary values/√3
V
AB
, V
BC
, V
CA
Phase-to-phase voltage
kV
V
Rated operating voltage of the primary values
V
0
Zero-sequence voltage
kV
V
Operating rated voltage of primary values/√3
V
NG
Neutral-point displacement
voltage
kV
V
Operating rated voltage of primary values/√3
f
Frequency
Hz
Hz
Rated frequency
Application and Setting Notes
i
i
NOTE
Before creating the protection functions in the function group, you should first connect hese functions to
the appropriate Circuit-breaker function group.
Parameter: Rated voltage
•
Default setting
(_:9421:102) Rated voltage
=
400.00 kV
With the
Rated voltage
parameter, you set the primary rated voltage. The
Rated voltage
set here is
the reference value for the percentage-measured values and setting values made in percentages.
Settings
Addr.
Parameter
C
Setting Options
Default Setting
Rated values
_:9421:102
General:Rated voltage
0.20 kV to 1200.00 kV
400.00 kV
5.4.3
5.4.4
Function-Group Types
5.4 Function-Group Type Voltage 3-Phase
SIPROTEC 5, High-Voltage Bay Controller, Manual
207
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...