Undervoltage Protection with Any Voltage
Setting Values
Measured value
Measured phase-to-ground voltage V
A
Measured phase-to-ground voltage V
B
Measured phase-to-ground voltage V
C
Measured phase-to-phase voltage V
AB
Measured phase-to-phase voltage V
BC
Measured phase-to-phase voltage V
CA
Calculated phase-to-phase voltage V
AB
Calculated phase-to-phase voltage V
BC
Calculated phase-to-phase voltage V
CA
Calculated voltage V0
Method of measurement
Fundamental component
RMS value
Threshold value
77
0.300 V to 340.000 V
Increments of 0.001 V
Time delay
0.00 s to 60.00 s
Increments of 0.01 s
Dropout ratio
1.01 to 1.20
Increments of 0.01
Dropout
The greater dropout differential (=
| pickup value – dropout value |
) of the following 2 criteria
applies:
Dropout differential derived from the parameter
Dropout ratio
If this parameter is not available, a dropout ratio of 95 % applies for the overvoltage and of 105 % for the
undervoltage functionality.
Minimum absolute dropout differential
150 mV sec.
Times
Operate time with time delay = 0 ms
Approx. 25 ms + OOT
78
at 50 Hz
Approx. 22 ms + OOT at 60 Hz
Dropout time
Approx. 20 ms + OOT
Frequency Operating Range
0.9 ≤ f/f
rated
≤ 1.1
According to specified tolerances
10 Hz ≤ f < 0.9 f
rated
1.1 f
rated
< f ≤ 80 Hz
Slightly expanded tolerances
f < 10 Hz
f > 80 Hz
Inactive, maintained;
Dropout of the pickup induced by blocking or by increasing the
measurand beyond the dropout threshold
Tolerances
Voltages
0.5 % of the setting value or 0.05 V
Time delays
1 % of the setting value or 10 ms
11.21
77
If you have selected the method of measurement = RMS value, do not set the threshold value under 10 V.
78
OOT (Output Operating Time): additional delay of the output medium used, see chapter
Technical Data
11.21 Undervoltage Protection with Any Voltage
1158
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...