Default setting
(_:14011:148) VT supervision time delay
=
10 s
With the
VT supervision time delay
parameter, you set the time for which exceeding the voltage
supervision threshold does not lead to a blocking.
Parameter: Circul. current blocking
•
Default setting
(_:14011:149) Circul. current blocking
=
on
With the
Circul. current blocking
parameter, you switch the supervision of the circulating reactive
current off or on.
Parameter: Circul. current threshold
•
Default setting
(_:14011:150) Circul. current threshold
=
150 %
With the
Circul. current threshold
parameter, you set the level at which the supervision must be acti-
vated.
Parameter: Circul. current time delay
•
Default setting
(_:14011:151) Circul. current time delay
=
30 s
With the
Circul. current time delay
parameter, you set the time for which exceeding the threshold
value of the circulating reactive current supervision does not lead to a blocking.
Settings
Two-Winding Transformer and Parallel Control
Addr.
Parameter
C
Setting Options
Default Setting
Ref. for %-values
_:2311:101
General:Rated current
0.20 A to 100000.00 A
1000.00 A
_:2311:102
General:Rated voltage
0.20 kV to 1200.00 kV
400.00 kV
_:2311:106
General:Rated app.
power transf.
0.20 MVA to 5000.00 MVA
692.82 MVA
_:2311:108
General:Imp(Z): short
circuit imp.
1.00 % to 20.00 %
10.00 %
General
_:14011:1
90V V.contr.2w:Mode
•
off
•
on
•
test
on
_:14011:101
90V V.contr.2w:Oper-
ating mode
•
Manual
•
Auto
Manual
Control tap changer
_:14011:107
90V V.contr.2w:Check
switching authority
•
no
•
yes
yes
_:14011:109
90V V.contr.2w:Control
model
•
direct w. normal secur.
•
SBO w. normal secur.
•
direct w. enh. security
•
SBO w. enh. security
SBO w. enh.
security
_:14011:110
90V V.contr.2w:SBO
time-out
0.01 s to 1800.00 s
30.00 s
_:14011:111
90V V.contr.2w:Feed-
back monitoring time
0.01 s to 1800.00 s
10.00 s
Voltage Control
_:14011:156
90V V.contr.2w:Number
of target voltage
•
1
•
2
•
3
•
4
1
6.9.5
Control Functions
6.9 Voltage Controller
SIPROTEC 5, High-Voltage Bay Controller, Manual
501
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...