The rule of three may be used to estimate the minimum dead time as follows:
360° = 10 s
120° = t
min
[fo_frequenzband, 1, en_US]
Set the parameter
T close without balancing
to a higher value, as in a practical case, the current
differential frequency is less than 0.1 Hz (for example, set point value 0.04 s).
At a differential frequency of 0.04 Hz, a 360° rotation takes 25 s and this leads to a minimum dead time of
approximately 8 s.
The example shows that the default setting of 5.00 s is a practicable value.
Parameter: Release for the kick pulse
•
Default setting
(_:149) Release for the kick pulse
=
off
With the parameter
Release for the kick pulse
, you can activate the kick pulse.
If you need a kick pulse for your application, change the default setting.
Parameter: Δf for the kick pulse
•
Default setting
(_:150) Δf for the kick pulse
=
0.04 Hz
With the parameter
Δf for the kick pulse
, you define the set point value for the kick pulse. The pulse
duration is derived from this.
Set the parameter
Δf for the kick pulse
to the same value as the parameter
Δf set point for
balancing
.
The setting value of 0.04 Hz leads to the following duration for the kick pulse:
[fo_frequency-adujsting-command_02, 1, en_US]
If the controller does not respond to this brief pulse (tfact < t pulse min), the minimum pulse
T f pulse
min
applies.
Parameter: Stabilization
•
Default setting
(_:151) Stabilization
=
no
If the dead time is too short, the parameter
Stabilization
results in a faster compensation of the speed
controller.
Parameter Value
Description
no
The default setting
no
is a practicable value for typical synchronization
applications.
yes
If the dead time is short, the transition process has not yet been completed
after a control pulse for the frequency. The frequency can fluctuate around
its set point value.
If you set the parameter
Stabilization
=
yes
, the transient status is
attenuated by canceling the control pulse or by issuing a control pulse in
the reverse direction in time.
Siemens only recommends this setting value if you wish to achieve fast
synchronization by means of short dead times or for special applications.
Control Functions
6.4 Synchronization Function
404
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...