Dropout time for 2 ≤ I/threshold value I ≤ 0.90
5 % of the reference (calculated) value
+2 % current tolerance or 30 ms
Influencing Variables for Thresholds
Transient excess pickup in method of measurement =
fundamental component, for τ > 100 ms (with
complete unbalance)
< 5 %
Stage with User-Defined Characteristic Curve
Setting Values
Method of measurement
Fundamental component
RMS value
–
Threshold value
1 A @ 50 and 100 Irated
0.010 A to 35.000 A
Increments of 0.001 A
5 A @ 50 and 100 Irated
0.05 A to 175.00 A
Increments of 0.01 A
1 A @ 1.6 Irated
0.001 A to 1.600 A
Increments of 0.001 A
5 A @ 1.6 Irated
0.002 A to 8.000 A
Increments of 0.001 A
Absolute pickup value
1 A @ 50 and 100 Irated
0.000 A to 35.000 A
Increments of 0.001 A
5 A @ 50 and 100 Irated
0.00 A to 175.00 A
Increments of 0.01 A
1 A @ 1.6 Irated
0.000 A to 1.600 A
Increments of 0.001 A
5 A @ 1.6 Irated
0.000 A to 8.000 A
Increments of 0.001 A
Dropout
Disk emulation
Instantaneous
–
Time multiplier
0.05 to 15.00
Increments of 0.01
Number of value pairs for the operate curve
2 to 30
Increments of 1
X values of the operate curve
1.00 p.u. to 20.00 p. u.
Increments of 0.01 p.u.
Y values of the operate curve
0.00 s to 999.00 s
Increments of 0.01 s
Number of value pairs for the dropout characteristic
curve
2 to 30
Increments of 1
X values of the dropout characteristic curve
0.05 p.u. to 0.95 p. u.
Increments of 0.01 p.u.
Y values of the dropout characteristic curve
0.00 s to 999.00 s
Increments of 0.01 s
Additional time delay
0.00 s to 60.00 s
Increments of 0.01 s
Dropout
The greater dropout differential (=
| pickup value – dropout value |
) of the following 2 criteria
applies:
Dropout
95 % of 1.1 ⋅ threshold value or 95 % of the absolute
pickup value
Minimum absolute dropout differential
Protection-class current transformer
15 mA sec. (I
rated
= 1 A) or
75 mA sec. (I
rated
= 5 A)
Instrument current transformer
0.5 mA sec. (I
rated
= 1 A) or
2.5 mA sec. (I
rated
= 5 A)
Reset of the Integration Timer
Instantaneous
With dropout
Disk emulation
Approx. < 0.90 ⋅ threshold value
11.9.3
Technical Data
11.9 Overcurrent Protection, Ground
SIPROTEC 5, High-Voltage Bay Controller, Manual
1131
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...