Additional Parameters for the Three-Winding Transformer and Grid Coupling Transformer: General
Winding 1
Parameter: Rated current
•
Default setting
(_:2311:101) Rated current
=
1000.00 A
Parameter: Rated voltage
•
Default setting
(_:2311:103) Rated voltage
=
400.00 kV
Winding 2
Parameter: Rated current
•
Default setting
(_:2311:102) Rated current
=
1000.00 A
Parameter: Rated voltage
•
Default setting
(_:2311:104) Rated voltage
=
400.00 kV
The measured values of the voltage controller can be displayed as primary values, secondary values, or in
percent. With the
Rated current
and
Rated voltage
parameters, you set the reference value for the
percentage values.
Tap Changer
The parameters of the tap changer inside the voltage controller correspond to those of the tap changer in
chapter
6.8.2 Application and Setting Notes
For the tap changer inside the voltage controller, the parameters for the control model are copies of those
from the voltage controller. This concerns the parameters:
•
Checking the switching authority
•
Control model
•
SBO
22
Time-out
•
Feedback.monitor.time
General
Parameter: Mode
•
Default setting
(_:14011:1) Mode
=
on
With the
Mode
parameter, you switch the voltage controller in
on
,
off
, or in
test
operation.
Parameter: Operating mode
•
Default setting
(_:14011:101) Operating mode
=
Manual
With the
Operating mode
parameter, you specify whether the controller is operating in
Auto
mode or in
Manual
mode.
Three-Winding Transformer only:
Parameter: Winding selection
•
Default setting
(_:15601:157) Winding selection
=
Winding 1
With the
Winding selection
parameter, you specify whether the controller controls the voltage of
Winding 1
or
Winding 2
. With the
WithMaxLoad
parameter, the voltage to be controlled is selected
automatically depending on the load current. With this method, you can toggle using the parameter
Winding selection
or the controllable
Automatic winding selection
.
If the controllable
Automatic winding selection
is set to Off or is not set, you can influence the
winding to be controlled using the following 2 options:
•
Using the
Winding selection
parameter
•
Using the
Manual winding selection
controllable
The function value
Active winding
shows the winding selection.
22
In the IEC 61850 standard, reservation is known as Select Before Operate (SBO).
Control Functions
6.9 Voltage Controller
SIPROTEC 5, High-Voltage Bay Controller, Manual
489
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...