The configuration dataset is transmitted 1x per minute. With the
Reporting Rate
parameter, you set the
number of cyclic repetitions of the data packages. As UDP is a connectionless protocol, a preconfigured desti-
nation device with its PDC/IP address is not required to be physically present and/or connected. This allows
uninterrupted provision of the data without bidirectional communication.
i
i
NOTE
If you have not configured valid PDC/IP addresses and still activate option for spontaneous data transmis-
sion, no cyclic data telegrams are sent.
i
i
NOTE
It is possible to configure IP addresses for various PDCs that are not in the same subnetwork as the COM
module. Such configurations are considered valid and may be loaded into the device. However, if the
device transmits spontaneous data and configuration packages to these IP addresses, the PDC with the
deviating subnetwork destination address cannot be reached.
EXAMPLE
COM-Module Address Configuration
•
IP address: 192.168.100.1
•
Subnet mask: 255.255.255.0
PDC Address Configuration
•
IP address for PDC1: 192.168.100.160
•
IP address for PDC2: 86.168.100.161
Only PDC1 receives the data because the IP address is in the same subnetwork as that of the COM module.
PDC2 cannot be reached because the subnetwork address (86.x) differs from the subnetwork address of the
COM module (192.x). The PMU cannot transmit data to this address.
Measuring-Point Assignment
After adding measuring points to the device, you can assign these measuring points to each configured PMU.
shows an example expansion of the device configuration by 2 additional input/output modules.
You connect the current and voltage inputs of these I/O modules to measuring points via the DIGSI routing
matrix, see example in
Measured Values, Energy Values, and Supervision of the Primary System
9.5 Phasor Measurement Unit (PMU)
SIPROTEC 5, High-Voltage Bay Controller, Manual
1011
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...