Pickup Mode
With the
Pickup mode
parameter, you define whether the protection stage picks up if all 3 measuring
elements detect the overvoltage condition (
3 out of 3
) or if only 1 measuring element detects the over-
voltage condition (
1 out of 3
).
Measured Value
Use the
Measured value
parameter to define whether the stage analyzes the phase-to-phase voltages V
AB
,
V
BC
, and V
CA
, or the phase-to-ground voltages V
A
, V
B
, and V
C
.
If the measured value is set to phase-to-phase, the function reports those measuring elements that have
picked up.
Pickup and Operate Curve
When the input voltage exceeds the threshold value by a settable value
Pickup factor
, the stage picks up
and the inverse-time characteristic curve is processed. Operate delay starts. The operate delay is the sum of
inverse-time delay and additional time delay.
Where
T
op
Operate delay
T
inv
Inverse-time delay
T
add
Additional time delay (parameter
Additional time delay
)
After pickup, the time value T
inv
is calculated for every input voltage that exceeds the threshold. An integrator
accumulates the value 1/T
inv
. Once the accumulated integral reaches the fixed value 1, the inverse-time delay
expires. The additional time delay T
add
starts. The stage operates after the additional time delay expires.
The inverse-time characteristic is shown in the following figure.
[dwovpinv, 2, en_US]
Figure 7-143
Operate Curve of Inverse-Time Characteristic
The inverse-time delay is calculated with the following formula:
Protection and Automation Functions
7.13 Overvoltage Protection with 3-Phase Voltage
790
SIPROTEC 5, High-Voltage Bay Controller, Manual
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...