Overview of Errors
Number
Device-Diagnosis Log
2822
Memory error (continuous)
Contact the Customer Support Center.
4727, 5018-5028
Hardware failure at module 1-12:
Contact the Customer Support Center.
4729
Device bus error (repeated):
•
Check the module configuration and the module connections.
•
Contact the Customer Support Center.
4733
Incorrect hardware configuration:
Synchronize the hardware configuration of the device with DIGSI.
5037-5048
Wrong module 1-12 detected:
Synchronize the hardware configuration of the device with DIGSI.
5031-5035
Identified wrong plug-in module on plug-in module position E/F/M/N/P:
Synchronize the hardware configuration of the device with DIGSI.
Wrong application configuration:
Search for the cause in the operational log and load a valid configuration to the device.
3640, 4514
Data-structure error:
Contact the Customer Support Center.
956
Firmware-version error:
Contact the Customer Support Center.
2013, 2025
Signature error:
Contact the Customer Support Center.
CFC error:
In DIGSI, check your CFC chart for the cause.
5050-5061
Binary-output error in module 1 - 12:
Contact the Customer Support Center.
5088, 5089
A missing display configuration was established:
Synchronize the hardware configuration of the device with DIGSI.
Defect Severity 4 (Group Alarm)
Errors of defect severity 4 are not device failures in the classical meaning. These errors do not affect the device
hardware and are not detected or reported by internal device supervision functions. The condition of the
defect severity 4 – the group alarm – is set user-specifically by the binary input signal
(_:503) >Group
alarm
. If the binary input signal is reset, the device is no longer in the
Group alarm
condition and all func-
tions return to the normal operating state.
If the group alarm is generated, the device reacts as follows:
•
The group indication
(_:300) Group alarm
is generated and recorded in the operational log.
•
The life contact is terminated.
•
The red Error LED is activated.
•
All protection and automation functions are blocked.
•
The device remains in operation, does not carry out any restart (reset), and does not switch to the safe
condition (Fallback mode).
•
The signals managed internally are marked with the
invalid
quality attribute. Signals managed inter-
nally are, for example, measured values, binary input and output signals, GOOSE and CFC signals.
In the delivery condition, every device has the CFC chart Process mode inactive, that initiates the Group
alarm (see chapter
).
8.8.5
Supervision Functions
8.8 Error Responses and Corrective Measures
SIPROTEC 5, High-Voltage Bay Controller, Manual
989
C53000-G5040-C015-9, Edition 11.2017
Summary of Contents for 6MD85
Page 8: ...8 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 30: ...30 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 46: ...46 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 172: ...172 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 514: ...514 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1056: ...1056 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1092: ...1092 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1204: ...1204 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1238: ...1238 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1252: ...1252 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...
Page 1256: ...1256 SIPROTEC 5 High Voltage Bay Controller Manual C53000 G5040 C015 9 Edition 11 2017 ...